On-line Double-conversion AC UPS 700VA – 3000VA

SENTINEL PRO is the latest evolution of the successful Riello Dialog Plus online UPS. This latest development has been designed with the environment in mind and is part of the Riello ECO Line of UPS. For long runtime applications, Sentinel Pro (ER models) can be fitted with matching battery extension packs which also include additional battery boost chargers.

The UPS is highly efficient. SENTINEL PRO is designed to save energy and has a power-off push-button feature to reduce energy consumption to zero, when no load is connected or switched off. Sentinel Pro models include 700VA, 1000VA, 1500VA, 2200VA and 3000VA.

In terms of communications, each Sentinel Pro has a built-in mimic panel with an LCD to show input and output voltages, and battery charge status. The inverter is a totally new design, fully microprocessor controlled and constructed to achieve the highest levels of operating efficiency and configuration options. SENTINEL PRO UPS also have USB communication ports as standard, with a built-in expansion slot for additional adapters, protocol converters and relate contact cards.

Features

  •  Filtered, stabilised, reliable output voltage: on-line double-conversion technology (VFI in accordance with IEC 62040-3) with built-in EMI filters
  • High overload capability up to 150%
  • Programmable auto-restart when mains power returns
  • Programmable cold-start from battery
  • Power factor correction (UPS input power factor close to 1)
  • Wide input voltage tolerance (from 120-280Vac) without battery usage
  • Possibility to extend autonomy for several hours
  • Fully configurable using UPS Tools configuration software
  • High level of battery reliability (automatic and manually-activated battery tests)
  • High level of UPS reliability (total microprocessor control)
  • Low impact on the mains (sinusoidal absorption)
  • Input protection with fuse which can be reset.

Advanced Communication

  • Advanced communication, multiplatform, for all operating systems and network environments, Powershield3 supervision and shut-down software included for Windows 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris and VMware ESX operating systems and other Unix operating systems
  • UPS Tools configuration and personalisation software supplied as standard
  • RS232 serial port and opto-isolated contacts
  • USB port
  • Slot for communication cards.
  • Input protection with fuse which can be reset.

Runtime Expandability 

Optional battery extension packs can be connected to increase UPS runtime. In addition, the Sentinel Pro range includes
ER versions with no internal batteries and more powerful battery chargers for longer runtimes.

Low Noise Level

Thanks to the use of high-frequency components and load-based fan speed control, the noise produced by the UPS is less than 40 dBA.

SERIES TABLE

ModelRated  PowerActive PowerWeightDimensions (WxDxH) (mm)
SEP 700700 VA560 W10,9 kg158 x 422 x 235
SEP 10001000 VA800 W13,3 kg158 x 422 x 235
SEP 1000 ER1000 VA800 W7 kg158 x 422 x 235
SEP 15001500 VA1200 W14,8 kg158 x 422 x 235
SEP 22002200 VA1760 W25,6 kg190 x 446 x 333
SEP 2200 ER2200 VA1760 W14 kg190 x 446 x 333
SEP 30003000 V2400 W28 kg190 x 446 x 333
SEP 3000 ER3000 VA2400 W15 kg190 x 446 x 333

SPECIFICATIONS TABLE

INPUT
Rated power(700-3000 VA)
Voltage220-230-240 Vac
Voltage tolerance140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
Maximum permitted voltage300 Vac
Frequency50/60 Hz
Frequency tolerance50 Hz ± 5% / 60 Hz ± 5%
Power factor> 0.99
Current distorsion≤7%
BY PASS
Voltage tolerance180 – 264 Vac
Frequency toleranceFrequency selected (from ±0.Hz to ±5Hz configurable)
Overload times125% for 5 seconds, 150% for 1 seconds
OUTPUT and INVERTER OUTPUT
Voltage distortion with linear load / with non-linear load< 2% / < 4%
FrequencyCan be selected: 50 Hz or 60 Hz or self-learning
Static variation± 1%
Dynamic variation ≤ 5% in 20 msec.
WaveformSinusoidal
Current crest factor3:1
Efficiency ECO and Smart Active Modes98%
BATTERIES
TypeVRLA AGM maintenance-free lead based; Supercaps
ENVIRONMENTAL
ColorBlack
CommunicationUSB / DB9 with RS232 and contacts / Slot for communication interface
Safety complianceEN 62040-1 and Directive 2006/95/EL
EMC conformanceEN 620040-2 category C2 and Directives 2004/108/EL
Accessories providedPower cable, IEC-IEC cable, USB cable, safety manual, quick start guide
Protection against overvoltage300 joule
Noise< 40 dBA @ 1 m
Operating temperature0°C / +40°C