MHE Rectifiers

Modular – Convection Cooled Rectifiers 2000W

The MHE rectifier utilizes Efore’s long experience and latest technology on high-performance industrial power supplies. MHE rectifiers are designed to meet demanding requirements of utility, industrial, rail and telecom applications with high efficiency and reliability requirements.

MHE rectifiers are convection cooled and require no fans. Rated output power is 2000W  in 48V – 220V output versions and 1500W in 24 V version. Rectifier input is single phase, range 85-300 VAC.

Rectifiers can be operated either with a VIDI+ system controller or as stand-alone modules with or without batteries in the output. The MHE is capable of sharing the output load in a maximum configuration of 48 paralleled units. It is also able to communicate status and operational parameters to the system control unit via the PowerCAN. An indicator light is located on the front panel of the unit indicating the operational status.

Constant Power and Constant Current Characteristics

The MHE rectifier provides constant output power characteristics. If the load rises above the maximum power, the output voltage decreases in order to maintain a constant output power. In addition, the maximum load current is limited, and above that level (Imax) the output voltage sinks rapidly. The voltage recovers automatically when the load is lower.

The maximum output power limit characteristics are scalable using the VIDI. The scaling parameter (together with many others) is stored in the rectifier’s permanent memory in order to ensure that the unit remembers the setting, even after a long power off.

Features

  • Efficiency up to 97 %
  • Convection cooled – no fans
  • MTBF 1 800 000 h @ 25oC, Telcordia SR-332
  • Output models 24, 48, 60, 110, 125, 220 VDC
  • 2000 W output power, 24 VDC 1500W
  • Lacquered PCB for rail and metro applications
  • Nominal Input voltage 100-250 VAC, range 85-300 VAC
  • Soft-start generator input feature
  • Active load current sharing
  • Internal over temperature protection
  • Digital communication over CAN bus with Efore VIDI controller
  • Flexible design with full front cabling
  • EMC:
    Generic EN 61000-6-1 / -2 / -3 / -4
    Power Utility EN61000-6-5
    Railway EN 50121-4, Telecom ETSI EN 300386
  • Safety:
    EN/IEC/UL 62368-1 (EN/IEC/UL 60950-1)
    EN 50124-1 Railway insulation coordination

 

 

Applications

  • Power Generation & Distribution
  • Railway Signalling & Substations
  • Industrial
  • Telecom
  • Military, Defense & Security

DC Systems with MHE Rectifiers

SERIES TABLE

Model  Output Power Voltage Range Maximum current
@ nominal output
Input Voltage VAC
MHE 24-1500 1500W 21-33 VDC 62.5 A @ 24 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC
MHE 48-1500 2000W 42-59 VDC 41.7 A @ 48 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC
MHE 60-2000 2000W 51-72 VDC 33.3 A @ 60 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC
MHE 110-2000 2000W 90-150 VDC 18.5 A @ 108 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC
MHE 125-2000 2000W 100-160 VDC 16.7 A @ 120 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC
MHE 220-2000 2000W 178-280 VDC 9.3 A @ 216 V Nominal 100VAC – 250VAC, rated full power range 180VAC – 275VAC