The 2RU MPS Ultra DC power system from ICT delivers up to 5.6 kilowatts of power in three factory pre-configured systems that make installation and setup a breeze.Available for 48, 24 or 12 volt DC applications, MPS Ultra systems are preconfigured at the factory to provide fast, easy installation at the site. With Ethernet-based remote monitoring and DC power control, advanced battery management features, integrated dual 100A battery breakers, and up to 12 fully managed load outputs that can be monitored and power-cycled remotely, the MPS Ultra provides unmatched capability for demanding wireless applications.
AC INPUT | |
Nominal system voltage | 120/240VAC |
Input voltage range | 100-300VAC |
Power factor (typical) | 0.99 |
Frequency | 50/60Hz |
DC OUTPUT | |
Check Out Datasheet Above | |
MECHANICAL | |
AC input connector | Terminal Block, #8 – #16 AWG |
DC output connector | Busbars with 5/16” bolts |
Remote alarm connectors | Terminal Block (#16 -24 AWG) |
Mounting | 2RU, 19 in rack mount |
Weight (Exc.Power Modules) | 30lbs / 13.6 kg |
Dimensions – H X W X L | 3.5 x 19.0 x 15.7 in. / 89 x 483 x 398 mm |
ENVIRONMENTAL | |
Operating temperature range | -30º to +60ºC |
Output derating | 2% / ºC (above 50º C) |
Storage temperature | -45º to +85ºC |
COMMUNICATIONS & CONTROL | |
Front Display | High resolution OLED with function keys |
Remote Communications | TCP/IP 10/100 Base-T |
I.P. Protocols | HTTP/HTTPS, SMTP, SNMPv1/v2c/v3 |
Inputs | 4 digital, 1 analog temp sensor contacts |
COMMUNICATIONS & CONTROL | |
Front Display | High resolution OLED with function keys |
Remote Communications | TCP/IP 10/100 Base-T |
I.P. Protocols | HTTP/HTTPS, SMTP, SNMPv1/v2c/v3 |
Inputs | 4 digital, 1 analog temp sensor contacts |
Monitoring functions | |
5.6KW model | AC input, DC output V and A, Power Module status, system current, alarms reporting |
2.8KW & 3.5KW models | AC input, DC output V and A, Power Module status, system current, battery voltage, battery current, state of charge, run time remaining, LVD status, load current monitoring, alarms reporting |
Control Functions | |
5.6KW model | Enable/disable DC outputs, adjust output voltage and current settings, auto restart delay time |
2.8KW & 3.5KW models | Enable/disable DC outputs, adjust output voltage and current settings, auto restart delay time, battery equalization, discharge test, LVD setpoints, power cycle load outputs, auto load-shedding, network watchdog, power-on sequencing, customizable input alarm labels and settings |
© Copyright Helios Power Solutions 2022