Master HE series is available from 100 to 800 kVA. The UPS feature a new on-line double-conversion technology utilising IGBT and DSP (Digital Signal Processor) control to provide maximum protection, power quality and green energy for any type of application including primary datacenters, disaster recover sites, telecoms rooms, industrial processes and security applications.
High efficiency stands for higher active power available if compared with legacy UPS thanks to output unitary p.f. Nominal power is granted with no downgrading independently from operating temperature.
Master HEP series UPS have a front panel graphic display providing UPS information, measurements, status updates and alarms in different languages, with wave form displays including voltage/current and provide a kWh reading that can be used to measure IT loads and calculate a datacenter PUE (power usage effectiveness) ratio.
Master HE series UPS include a range of features designed to prolong battery life and reduce their usage.
Master HE has a zero impact on connected power sources – grid networks or generators:
≤ 3% input current distortion
Input power factor 0,99
power walk-in function – to ensure a progressive rectifier start-up
start-up delay function – to restart the rectifier when the mains power supply is restored.
Smart Grid Ready UPS
Master HE series UPS are ‘Smart Grid Ready’ and can be used within an energy storage solution, whilst simultaneously operating at the highest levels of efficiency and automatically selecting the most efficient operating mode based on the state of the lower grid network or generator supply. The UPS are designed to electronically interface with energy management systems within an ‘intelligent’ Smart Grid application.
MODEL | NOMINAL POWER (kVA) | ACTIVE POWER (kW) | NOMINAL VOLTAGE |
MHE 100 | 100 | 100 | 380 – 400 – 415 Vac three-phase |
MHE 120 | 120 | 120 | 380 – 400 – 415 Vac three-phase |
MHE 160 | 160 | 160 | 380 – 400 – 415 Vac three-phase |
MHE 200 | 200 | 200 | 380 – 400 – 415 Vac three-phase |
MHE 250 | 250 | 250 | 380 – 400 – 415 Vac three-phase |
MHE 300 | 300 | 300 | 380 – 400 – 415 Vac three-phase |
MHE 400 | 400 | 400 | 380 – 400 – 415 Vac three-phase |
MHE 500 | 500 | 500 | 380 – 400 – 415 Vac three-phase |
MHE 600 | 600 | 600 | 380 – 400 – 415 Vac three-phase |
MHE 800 | 800 | 800 | 380 – 400 – 415 Vac three-phase |
INPUT | |
Voltage | 380 – 400 – 415 Vac three-phase |
Soft start | 0 – 100% in 120’’ (selectable) |
Frequency | 45 – 65 Hz |
Frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) |
Power factor at full load | > 0.99 |
Current distorsion | thdi ≤ 3% |
BY PASS | |
Nominal Voltage | 380 – 400 – 415 Vac three-phase + N |
Nominal Frequency | 50 or 60 Hz (selectable |
OUTPUT | |
Number of phases | 3 + N |
Nominal voltage | 380 – 400 – 415 Vac three-phase + N (selectable) |
Frequency | 50 Hz / 60 Hz |
Static stability | ± 1% |
Voltage distortion | < 1% with linear load / < 3% with non-linear load |
Overload | 110% for 60’; 125% for 10’; 150% for 1’ |
BATTERIES | |
Ripple current | Zero |
Type | VRLA AGM/GEL |
Recharge voltage compensation | -0,5 Vx°C |