Master FC400 series static frequency converters are available from 30kVA to 125 kVA, with 50 or 60 Hz input and 400 Hz output. The result of extensive experience acquired in the UPS industry, the Master FC 400 series is distinguished by the use of technologically advanced components and for excellent reliability, ease of maintenance and ease of operation.
The Master FC400 series uses double conversion technology (VFI SS 111 voltage and frequency independent compliant with IEC EN 62040-3), with an integrated output transformer to ensure the galvanic isolation of the load from mains disturbances under all conditions.The output voltage is 208 Vac three-phase (adjustable 200-215 Vac).Thanks to high-frequency IGBT technology and digital control, Master FC400 frequency converters are ideal for airport, military and naval applications.
The Master FC400 was designed to reduce to a minimum the impact on the mains or generator located upstream, thanks to the low harmonic content input and the progressive start of the rectifier. These features make the Master FC400 frequency converters especially compatible with generators.
The Master FC400 requires a small space for installation (only 0.86m2 for a 125kVA model).
The main assemblies of the UPS can be easily accessed for maintenance, via the removable front panel. Fans located in the top of the UPS cabinet, eliminate the need for side or rear access, and allow the UPS to be placed against a wall.
Master FC400 provides additional protection for a wide range of applications, including:
MODEL | NOMINAL POWER (kVA) | ACTIVE POWER (kW) | NOMINAL INPUT VOLTAGE |
MFC 30 | 30 | 24 | 380 – 400 – 415 Vac three-phase |
MFC 60 | 60 | 48 | 380 – 400 – 415 Vac three-phase |
MFC 80 | 80 | 64 | 380 – 400 – 415 Vac three-phase |
MFC 100 | 100 | 80 | 380 – 400 – 415 Vac three-phase |
MFC 125 | 125 | 100 | 380 – 400 – 415 Vac three-phase |
INPUT | |
Voltage | 380 – 400 – 415 Vac three-phase |
Soft start | 0 – 100% in 120’’ (selectable) |
Frequency | 45 – 65 Hz |
Frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) |
Power factor at full load | > 0.99 |
Current distorsion | < 5% C (HC Version) |
OUTPUT | |
Number of phases | 3 + N |
Nominal voltage | 208 Vac three-phase + N |
Frequency | 400 Hz |
Static stability | ± 1% |
Voltage distortion | < 3% with linear load / < 4% with non-linear load |
Overload | 110% for 60’; 125% for 10’; 150% for 1’ |
© Copyright Helios Power Solutions 2022