DNR120-960TS Series – AC/DC 3ph input : Single Output 120W – 960W

Brand: XP POWER

SKU: HPS-PS-DIN-DNR120-960TS-SERIES
This product is available globally.
  • Three Phase AC Input 340 – 575VAC
  • 5V,12V, 24, & 48V output voltage options
  • Up to 93% Efficiency
  • Wide Adjustment Range
  • Full Power -40 °C to +60 °C
  • This product has been discontinued, below models number are last available in stock

Product Range

SKU Power AC/DC Input Voltage AC/DC Output Voltage 1 AC/DC
DNR120TS12120W340 - 575VAC12V
DNR120TS24120W340 - 575VAC24V
DNR960TS48-I960W340 - 575VAC48V

Description

DNR120-960TS Series

Three Phase Input – DIN-Rail AC/DC Power Supply

AC/DC Rail Din Power Supply Three Phase AC Input up to 960W

  • Three Phase AC Input
  • Up to 93% Efficiency
  • Wide Adjustment Range
  • Full Power -40 °C to +60 °C
  • Rugged Design for Industrial Applications
  • Single Phase Input Operation (340 575 VAC)
  • 3 Year Warranty

Additional information

WeightN/A
DimensionsN/A

SERIES TABLE

Model InputOutputPower
DNR120TS12340 to 575 Vac12 V / 10 A120W
DNR120TS24340 to 575 Vac24 V / 5 A120W
DNR240TS24-I340 to 575 Vac24 V / 10 A240W
DNR240TS48-I340 to 575 Vac48 V / 58 A240W
DNR480TS24-I340 to 575 Vac24 V / 20 A480W
DNR480TS48-I340 to 575 Vac48 V / 10 A480W
DNR960TS24-I340 to 575 Vac24 V / 40 A960W
DNR960TS48-I340 to 575 Vac48 V / 20 A960W

SPECIFICATIONS TABLE

Dimensions:DNR120TS: 4.39 x 2.93 x 4.87 in (111.3 x 74.3 x 123.6 mm)
DNR240TS: 4.39 x 3.50 x 4.87 in (111.3 x 89.0 x 123.6 mm)
DNR4800TS: 4.39 x 5.91 x 4.87 in (111.3 x 150.0 x 123.6 mm)
DNR960TS: 4.39 x 10.86 x 4.96 in (111.3 x 275.7 x 125.9 mm)
Input Voltage:340-575 VAC 3 phase (single phase operation with 75% of rated output), 480-820 VDC
Harmonic Currents:EN61000-3-2, class A
Efficiency:87-93%
Operating Temp: -40 °C to 70 °C (DNR480TS -30 °C), derate linearly from 60 °C at 2.5%/°C (3.5%/°C for DNR960TS), start up at -35 °C (DNR480TS -20 °C), see datasheet
Isolation:3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
European Safety Approvals:EN60950-1
US Safety Approvals:UL508 UL60950-1 Pollution Degree 2,
UL60950-1 Overvoltage Category II UL508 Overvoltage Category III, ANSI/ISA 12.12.01 Class 1, Division 2, Groups A,B,C and D
EMC:EN55022, class B conducted & radiated

View Datasheet