Smartcharger 500W And 750W

Helios Power Solutions Smart Battery Chargers or also known as Boost Chargers, are able to respond to the condition of a battery, modifying their charging actions accordingly. Our Smart Chargers are microprocessor controlled and allow for the maximum charge into your batteries to minimize the charge time. Boost mode allows for a high current, high voltage charging cycle, also allowing for the maximum charge into the battery in the shortest possible time. Float mode allows for the battery to be held at optimal voltage with a small trickle charge still being generated, to ensure that the battery is ready to when used.
Other features of our Smart Chargers include:
  • Designed to charge both sealed and flooded lead-acid battery types
  • Come with temperature compensation to ensure that the correct voltage is applied to the battery, irrelevant of the ambient temperature
  • Provide fully automatic battery recovery in the shortest possible time
  • Includes with both ‘boost’ and ‘float’ mode

A simple charger works by supplying a constant DC source to a battery being charged. The simple charger does not alter its output based on time or battery charge. This simplicity means that simple chargers are very cheap, although there is a trade-off in quality. A trickle charger is typically a low current battery charger, used to charge small capacity batteries.

 

SERIES TABLE

ModelOutput Voltage¹ (float V)Output Voltage¹ (max boost A)Output Current (continuous A)Min – Max Battery (Ah)Size  
SR500E1213.814.734130-600
SR500E2427.629.41765-300
SR500E3641.444.111.344-200
SR500E4855.258.88.530-150
SR500E72*82.888.65.622-95
SR500E91 *110.4117.64.216-75
SR500E92 *124.2132.83.715-65
SR500E93 *1381473.413-60
SR750E1213.814.750200-900
SR750E2427.629.425100-450
SR750E3641.444.116.766-300
SR750E4855.258.812.550-220
SR750E72*82.888.6627-120
SR750E91 *110.4117.66.225-110
SR750E92 *124.2132.85.622-100
SR750E93 *138147520-90
* Note: High voltage versions  SR750B72, 91, 92, 93 have  a manual  boost function.  Initiation of boost charge is by pushing the BOOST switch or relay contact. Termination of boost charge is by manual push button (FLOAT or STANDBY) or by the time set by the internal timer (BT setting).   They do not have a current terminated boost function.

SPECIFICATIONS TABLE

ELECTRICAL
InputSTANDARD: 180V – 264VAC
OPTIONAL: 88V – 132VAC
Frecuency50 or 60Hz ( to be specified at time of order)
FusingInternal AC input fuse
Isolation1KV DC input – output / earth
Efficiency> 85%
Inrush currentSoft start circuit
Output voltagesRefer to the model table
Voltage adj. rangeApprox 95 – 105% of V nominal
Temp. CompensationTemperature sensor on 1.7m lead with adhesive pad:  -4mV / °C / cell ±10%
Current LimitConstant current limit on overload & short circuit
Output ProtectionAutomatic shutdown if battery leads reversed or short circuit on output
Line regulation< 0.2% over AC input range
Load regulation< 0.4% open circuit to 100% load
Noise<1%
Drift<0.1%
Hold-up time15 – 20 ms (nom. – max. Vin) without  battery
OVPOver-voltage protection on output at ~ 130% of nominal output voltage
Thermal ProtectionYes
Alarm & boost/float indication relays*Mains fail
Batt low (set at 1.83V/cell = 11, 22V, etc)
Boost/float
Alarm Relay ContactsC – NO – NC  full changeover   Rated 1A @ 50V DC or 32VAC
Output VoltsMay be adjusted to suit batery specifications
Adjustable ParametersAll firmware parameters listed under features may be adjusted at time of ordering
FEATURES
Switch/ LED Indication & functionsBOOST:  Red
FLOAT:  Green
STANDBY: Red (Push button to turn output off/on).
Refer to instruction manual  for full list of LED Operation codes
Factory Programmable parameters (default settings shown in brackets; please note that some parameters are interdependent of each other)*1Start up in boost or float mode (Boost)
Current terminated boost  (Yes)
Current initiated boost  (Yes)
Start boost on mains return (Yes)
Pre-boost state timer 1-255 minutes (1)
Max boost charge time 1-48 hours (24)
Pre-float state timer 1-255 minutes (1)
Resume prior state upon mains return timer 1-255 minutes (10)
Resume on boost charge upon mains return 0-255 hours (24)
Pre-forced float timer 1-255 minutes (1)
Delay before mains fail recognition 4sec – 8.5minutes(5 minutes)
*1 except high voltage versions
SR500-750E - Smartcharger 500W And 750W boost charger SR 500E – SR 750E &#8211...