Our website features a wide range of standard power conversion and backup products, but we also have the capacity and capability to design and manufacture custom solutions to meet your specific application needs. Contact our team of experienced engineers today to discuss your project. Dismiss
Smartcharger 500W And 750W
A simple charger works by supplying a constant DC source to a battery being charged. The simple charger does not alter its output based on time or battery charge. This simplicity means that simple chargers are very cheap, although there is a trade-off in quality. A trickle charger is typically a low current battery charger, used to charge small capacity batteries.
Model | Output Voltage¹ (float V) | Output Voltage¹ (max boost A) | Output Current (continuous A) | Min – Max Battery (Ah)Size |
SR500E12 | 13.8 | 14.7 | 34 | 130-600 |
SR500E24 | 27.6 | 29.4 | 17 | 65-300 |
SR500E36 | 41.4 | 44.1 | 11.3 | 44-200 |
SR500E48 | 55.2 | 58.8 | 8.5 | 30-150 |
SR500E72* | 82.8 | 88.6 | 5.6 | 22-95 |
SR500E91 * | 110.4 | 117.6 | 4.2 | 16-75 |
SR500E92 * | 124.2 | 132.8 | 3.7 | 15-65 |
SR500E93 * | 138 | 147 | 3.4 | 13-60 |
SR750E12 | 13.8 | 14.7 | 50 | 200-900 |
SR750E24 | 27.6 | 29.4 | 25 | 100-450 |
SR750E36 | 41.4 | 44.1 | 16.7 | 66-300 |
SR750E48 | 55.2 | 58.8 | 12.5 | 50-220 |
SR750E72* | 82.8 | 88.6 | 6 | 27-120 |
SR750E91 * | 110.4 | 117.6 | 6.2 | 25-110 |
SR750E92 * | 124.2 | 132.8 | 5.6 | 22-100 |
SR750E93 * | 138 | 147 | 5 | 20-90 |
* Note: High voltage versions SR750B72, 91, 92, 93 have a manual boost function. Initiation of boost charge is by pushing the BOOST switch or relay contact. Termination of boost charge is by manual push button (FLOAT or STANDBY) or by the time set by the internal timer (BT setting). They do not have a current terminated boost function. |
ELECTRICAL | |
Input | STANDARD: 180V – 264VAC |
OPTIONAL: 88V – 132VAC | |
Frecuency | 50 or 60Hz ( to be specified at time of order) |
Fusing | Internal AC input fuse |
Isolation | 1KV DC input – output / earth |
Efficiency | > 85% |
Inrush current | Soft start circuit |
Output voltages | Refer to the model table |
Voltage adj. range | Approx 95 – 105% of V nominal |
Temp. Compensation | Temperature sensor on 1.7m lead with adhesive pad: -4mV / °C / cell ±10% |
Current Limit | Constant current limit on overload & short circuit |
Output Protection | Automatic shutdown if battery leads reversed or short circuit on output |
Line regulation | < 0.2% over AC input range |
Load regulation | < 0.4% open circuit to 100% load |
Noise | <1% |
Drift | <0.1% |
Hold-up time | 15 – 20 ms (nom. – max. Vin) without battery |
OVP | Over-voltage protection on output at ~ 130% of nominal output voltage |
Thermal Protection | Yes |
Alarm & boost/float indication relays* | Mains fail |
Batt low (set at 1.83V/cell = 11, 22V, etc) | |
Boost/float | |
Alarm Relay Contacts | C – NO – NC full changeover Rated 1A @ 50V DC or 32VAC |
Output Volts | May be adjusted to suit batery specifications |
Adjustable Parameters | All firmware parameters listed under features may be adjusted at time of ordering |
FEATURES | |
Switch/ LED Indication & functions | BOOST: Red |
FLOAT: Green | |
STANDBY: Red (Push button to turn output off/on). Refer to instruction manual for full list of LED Operation codes | |
Factory Programmable parameters (default settings shown in brackets; please note that some parameters are interdependent of each other)*1 | Start up in boost or float mode (Boost) |
Current terminated boost (Yes) | |
Current initiated boost (Yes) | |
Start boost on mains return (Yes) | |
Pre-boost state timer 1-255 minutes (1) | |
Max boost charge time 1-48 hours (24) | |
Pre-float state timer 1-255 minutes (1) | |
Resume prior state upon mains return timer 1-255 minutes (10) | |
Resume on boost charge upon mains return 0-255 hours (24) | |
Pre-forced float timer 1-255 minutes (1) | |
Delay before mains fail recognition 4sec – 8.5minutes(5 minutes) | |
*1 except high voltage versions |