The BCH300 & BCH500 series battery charger is a rugged, industrial-grade product, using field- proven design suitable for use in DC battery back-up applications. It is a mature product providing excellent reliability and performance and delivering 300 / 500 watts of output power with convection/conduction cooling. – NO Fans.
The two alarms provide external monitoring of Power Fail / Charger Fail and Battery Low via voltage free contacts.
The chassis-mount design feature allows for easy mounting.
Additional ruggedizing and conformal coating are available for applications requiring higher immunity to shock, vibration, humidity, moisture, dust and insects
Options
Model | Output Nom | Float V | Current | Power |
RM-BCH300-14FT | 12 V | 13.8 V | 20A | 300W |
RM-BCH300-28FT | 24 V | 27.6 V | 11A | 300W |
RM-BCH300-55FT | 48 V | 55.2 V | 5.5A | 300W |
RM-BCH300-110FT | 96 V | 108 V | 2.5A | 300W |
RM-BCH300-110FT | 108 V | 124 V | 2.5A | 300W |
RM-BCH500-28FT | 24 V | 27.6 V | 18A | 500W |
RM-BCH500-55FT | 48 V | 55.2 V | 9A | 500W |
RM-BCH500-110FT | 96 V | 108 V | 4A | 500W |
RM-BCH500-110FT | 108 V | 124 V | 4A | 500W |
For Digital Meters, change part no to: RMM-BCH300-xxx RMM-BCH500-xxx | ||||
110V model adjustable for use on 96V or 108V nominal battery systems |
Input Voltage | 230VAC ( 190 ~ 264 ) |
Input Frequency | 47 ~ 63Hz |
Input Current | BCH300 @ 2.8A |
BCH500 @ 4.7A | |
Input Protection | Inrush current limiting Transient protection / Varistors Internal safety fuse |
Output Voltage | Refer to table |
Overload Protection | Constant current limiting with short circuit protection.Battery must be externally fused. |
Efficiency | Typically 80% |
Overvoltage Protection | Yes. Recycle mains input to re-set |
Parallel Operation | Yes. Recycle mains input to re-set |
Current Limit | Primary side power limited |
Operating Temp. | 0ºC to +50ºC at full load. Derate 2.5% per ºC to +70ºC. |
Cooling | Conduction / convection cooled via base plate |
Humidity | 5-95% non-condensing |
Ripple & Noise | Typically <1% of output voltage |
Insolation | Input-Output: 3Kvac, Input-Frame Ground: 2kVAC Output-Frame Ground: 500VAC. |
EMC | EN55022 Class A |
Immunity | EN 61000-4-2 (ESD) EN 61000-4-3 (RF Immunity) EN 61000-4-4 (Fast Transients) EN 61000-4-6 (Conducted Imm.) |
MTBF | >150,000hrs @ 45ºC |
Dimensions | 2U x 19in x 420mm Rack Mount |
© Copyright Helios Power Solutions 2022