Our website features a wide range of standard power conversion and backup products, but we also have the capacity and capability to design and manufacture custom solutions to meet your specific application needs. Contact our team of experienced engineers today to discuss your project. Dismiss
Surges and voltage transients are a major cause of expensive electronic equipment failure and business disruption. Damage may result in the loss of capital outlays, such as computers and communications equipment, as well as consequential loss of revenue and profits due to unscheduled system down-time.
nVent ERICO offers multiple series of surge protective devices (SPDs) suitable for a vast range of applications that provide reliable protection from voltage transients on power distribution systems.
The EDT2 Series Enhanced Transient Discriminating Surge Protective Devices provide reliable protection against voltage transients within the IEC Class II and UL Type 1CA environments. In addition, nVent ERICO’s Transient Discriminating (TD) technology ensures continued operation during and after sustained and abnormal over-voltage events. Tested and independently certified to the IEC and UL standards, the EDT2 Series provides a range of safety and performance features for the harshest environments and suitable for protection within a wide range of applications. The EDT2 Series provides extended service life in the harshest of environments, ensuring your equipment and systems are kept safe and operational through extreme abnormal voltage conditions.
Tested with shorter duration current impulses. These SPDs would be installed where the surge currents are expected to be less. This could be at the main power entry point of a building in a non-exposed location (surrounded by taller buildings, for example), or at sub-panels within the building.
Part Number | EDT255010R |
Nominal System Voltage (Un) | 400 V |
Max Continuous Operating Voltage (Uc) | 550 V |
Nominal Discharge Current (In), IEC | 20 kA 8/20 μs |
Max Discharge Current (Imax), IEC | 50 kA 8/20 μs |
Voltage Protection Level (Up) | 2,500 V |
Back-Up Fuse @ Isccr | 250 A @ 50 kA |
315 A @ 25 kA | |
Response Time | 25 ns Max |
Protection Modes | L-PE N-PE L-PEN L-N |
Short Circuit Current Rating (Isccr) | 25 kA 50 kA |
Temporary Over Voltage 120 min (Ut/mode) | 918 V withstand |
Nominal Discharge Current (In), UL | 20 kA 8/20 μs |
Short Circuit Current Rating (SCCR) | 200 kA |
Voltage Protection Rating (VPR) | 1,800 V |
Technology | Thermal Disconnect |
Connection, Solid | 35 mm² Max |
Connection, Stranded | 25 mm² Max |
Torque (TQ) | 4.5 N-m |
Humidity | 5 – 95 % RH |
Temperature | -40 to 70 °C |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 |
Mounting | 35 mm top hat DIN rail |
Remote Contact Switching Capacity | 1.0 A @ 250 VAC |
1.0 A @ 125 VAC | |
0.5 A @ 48 VDC | |
0.5 A @ 24 VDC | |
0.5 A @ 12 VDC | |
Remote Contacts | Yes |
Status Indication | Mechanical flag |
Depth (D) | 69 mm |
Height (H) | 90 mm |
Width (W) | 18 mm |
Unit Weight | 0.155 kg |
Certification Details | UL® 1449 Edition 4 Type 1CA |
Complies With | EN 61643-11 Type 2 |
IEC® 61643-11 Class II |