Bravo 25 Modular Inverters 380Vdc 3kVA

BRAVO is a compact and scalable modular inverter providing a pure sine wave AC supply. In conjunction with a DC Power system, it provides an excellent AC backup solution. It uses the latest inverter technology, providing superior energy efficiency in a compact size.


The ECI technology eliminates all single points of failure with full scalability; up to 32 modules in parallel and high efficiency of up to 96% in AC to AC conversion, and above 94.5% in DC/AC conversion, hence reducing operating costs.

Applications

All business critical applications and all types of AC loads.

The design is modular and scalable with hot- swappable inverter modules which ensures low Mean Time to Repair (MTTR), reduction in service costs and meets the changing needs for future expansion.

SPECIFICATIONS TABLE

Power
AC Output Power
Nominal Output power (VA) / (W)3000 VA / 2500 W
Short time overload capacity125% (15 seconds)
Admissible load power factorFull power rating from 0 inductive to 0 capacitive
DC Input Specifications
DC voltage: Nominal / range336 V / 200 V – 400 V*
Nominal current (at 48 Vdc and 2400 W output)7.9 A
Maximum input current (for 15 second) / voltage ripple9.9 A / < 250 mV RMS
AC Input Specifications
Nominal voltage (AC)120 Vac / 208 Vac / 230 Vac / 277 Vac Line to Neutral
Voltage range (AC)108 – 290 Vac permament (295 Vac 60 ms)
Brownout1500 VA / 1500 W @120 VAC, 2500 VA / 2500 W @190 VAC, 3000 VA / 2500 W from 230 VAC to
277 Vac
Power factor> 99%
Frequency range (selectable) / synchronization range50 Hz (range 47 – 53 Hz) / 60 Hz (range 57 – 63 Hz)
AC Output Specifications
Nominal voltage (AC**)120 Vac / 208 Vac / 230 Vac / 277 Vac
Frequency / frequency accuracy50 or 60 Hz / 0.03%
Total harmonic distortion (resistive load)< 3%
Load impact recovery time (10% – 90%)<= 0.4 ms
Nominal current13 A @ 230 Vac
Crest factor at nominal power3 : 1 for load P.F. <=0.7
Short circuit clear up capacity 0-20 ms100 A for 20 ms – Available while Mains is available at AC input port / 34 A RMS in DC/AC
Short circuit current after >20 ms -15 s18 A RMS
AC output voltage stability ±1% from 10% to 100% load
In Transfer Performance
Max. voltage interruption / total transient voltage duration (max)0 s / 0 s
Signaling & Supervision
DisplaySynoptic LED
Alarms output / SupervisionDry contacts on shelf / Use optional devices
Remote on / offOn rear terminal of the shelf via T2S ETH
EMCEN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8
ETSI EN 300386 v1.9.1
SafetyEN62040-1
CoolingForced
MTBF240 000 hrs (MIL-217IF)
Efficiency (Typical): Enhanced power conversion / on line96% / >92.5%
Dielectric strength DC/AC2100 Vdc
RoHSCompliant
EnvironmentETSI EN 300019 / ETSI EN 300132.2
Altitude above sea without de-rating of power< 1500 m / derating > 1500 m – 0.8 % per 100 m / max 4000 m
Ambient temperature -20 to 40° C
derating from 40°C to 65°C
Storage temperature / relative humidity -40 to 70°C / 95%, non-condensing
Material (casing)Zinc coated steel
Modular Inverters Bravo ECI 380 Vdc 3kVA Bravo 25 Modular Inverters: 38...