Our website features a wide range of standard power conversion and backup products, but we also have the capacity and capability to design and manufacture custom solutions to meet your specific application needs. Contact our team of experienced engineers today to discuss your project. Dismiss
Surges and voltage transients are a major cause of expensive electronic equipment failure and business disruption. Damage may result in the loss of capital outlays, such as computers and communications equipment, as well as consequential loss of revenue and profits due to unscheduled system down-time. nVent ERICO offers multiple series of surge protective devices (SPDs) suitable for a vast range of applications that provide reliable protection from voltage transients on power distribution systems. The DT2 Series DIN Rail Surge Protective Devices provide reliable and efficient protection against voltage transients within the IEC Class II and UL Type 1CA environments. Tested and independently certified to the IEC and UL standards, the DT2 Series provides a range of safety and performance features for the harshest environments and suitable for protection within a wide range of applications.
Part Number | DT230040R |
Nominal System Voltage (Un) | 240 V |
Max Continuous Operating Voltage (Uc) | 300 V |
Nominal Discharge Current (In), IEC | 20 kA 8/20 μs |
Max Discharge Current (Imax), IEC | 50 kA 8/20 μs |
Voltage Protection Level (Up) | 1,500 V |
Back-Up Fuse @ Isccr | 250 A @ 50 kA |
315 A @ 25 kA | |
Response Time | 25 ns Max |
Protection Modes | L-PEN N-PE |
Short Circuit Current Rating (Isccr) | 25 kA |
50 kA | |
Temporary Over Voltage 120 min (Ut/mode) | 442 V Safe Fail |
Temporary Over Voltage Withstand 5 s (Ut) | 337 V |
Nominal Discharge Current (In), UL | 20 kA 8/20 μs |
Short Circuit Current Rating (SCCR) | 150 kA |
Voltage Protection Rating (VPR) | 1,200 V |
Technology | Thermal Disconnect |
Connection, Solid | 35 mm² Max |
Connection, Stranded | 25 mm² Max |
Torque (TQ) | 4.5 N-m |
Humidity | 5 – 95 % RH |
Temperature | -40 to 70 °C |
Enclosure Material | UL® 94V-0 Thermoplastic |
Enclosure Rating | IP 20 |
Mounting | 35 mm top hat DIN rail |
Remote Contact Switching Capacity | 1.0 A @ 250 VAC |
1.0 A @ 125 VAC | |
0.5 A @ 48 VDC | |
0.5 A @ 24 VDC | |
0.5 A @ 12 VDC | |
Remote Contacts | Yes |
Status Indication | Mechanical flag |
Depth (D) | 69 mm |
Height (H) | 90 mm |
Width (W) | 72 mm |
Unit Weight | 0.505 kg |
Certification Details | UL® 1449 Edition 4 Type 1CA |
Complies With | EN 61643-11 Type 2 |
IEC® 61643-11 Class II |
© Copyright Helios Power Solutions 2024