The ICT240DB-8IRC provides high current 48, 24 and 12 volt DC dual bus DC distribution capability for sites requiring IP-based remote monitoring and power control of connected loads where front access to all connections and functions is required. Each bus is rated at 120 Amps peak and provides four breaker-protected outputs. TCP/IP remote management and power control are standard, allowing remote monitoring of individual loads as well as power-cycling, rebooting, and load shedding of individually selected outputs. The integrated web server provides an intuitive, easy to use browser interface, and SNMP v1/v2c/v3 is supported.
The ICT240DB-8IRC Front Access DC Distribution Panel provides a dual bus, common ground 1RU solution for applications requiring remote monitoring and power control of individual loads. The on-board TCP/IP and web server provide an easy to use, graphical user interface for remote management and power control of system and individual outputs. Each bus supports up to four 30A hydraulic/magnetic breakers for 48, 24, or 12 volts DC.
Dual voltages and polarities can be supported on a single panel, useful for sites requiring -48 and +24 volts DC to be distributed simultaneously.Alarms can be sent to multiple email accounts, and each output has definable load-shed settings. The network watchdog feature will ping a pre-determined I.P. address, such as a router, and power-cycle the device if not answered.There are four digital inputs for connecting site monitoring sensors such as door, fire, and water alarms, and one dedicated temperature sensor input. These alarms can be given individual names and be sent as email alarm notifications.
The on-board web server means there is no software to maintain, and SNMP is also supported. Firmware can be updated remotely over the Ethernet link.The ICT240DB-8IRC allows each connected load to be monitored, power cycled, or taken off-line. This functionality can be used to conserve power, troubleshoot devices, and reboot connected loads remotely, possibly preventing or delaying the need for an costly site visit.
Model | Description |
ICT240DB-8IRC | Front access dual bus common ground DC distribution panel |
ICT-CB5(1) | 5 Amp hydraulic/magnetic breaker |
ICT-CB10(1) | 10 Amp hydraulic/magnetic breaker |
ICT-CB15(1) | 15 Amp hydraulic/magnetic breaker |
ICT-CB25(1) | 25 Amp hydraulic/magnetic breaker |
ICT-CB30(1) | 30 Amp hydraulic/magnetic breaker |
ICT-BLP(1) | Breaker Position Blanking Plate |
ICT-TMP(2) | Temperature Sense Probe with 3M (10ft) cable |
ICT-RA2319(2) | ICT 23 to 19 inch, 1RU rack mount reducer kit |
(1) Hydraulic/magnetic breakers and blanking plates not included, must be ordered separately. (2) Option, orderable separately |
Power Specifications | |
Operating Voltage Range (pos or neg ground) | 10-60VDC |
System Current Rating (peak/cont) | 240A / 200A |
A/B Bus Current Rating (peak/cont) | 120A / 100A |
Number of Outputs per Bus | 4 |
Output Rating, continuous (12, 24V, 48V) | 25A |
Communications and Control | |
Ethernet | TCP/IP built-in web server and graphical user interface, 10/100BASE-T, IEEE 802.3 compatible |
Supported Protocols | IPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMP v1/v2c |
SNMP Ports | UDP Port 161, SNMP Traps: UDP Port 162 |
Firmware Upgrades | Upgradeable over Ethernet |
Security | Password protection, HTTPS encryption, TLS 1.0 |
8 Channel Output Monitoring | Current draw measured and reported for each output, user definable under and over current alarms |
Email and SMS Alerts | Multiple email or text accounts, adjustable intervals |
Data Logging | Up to 30 days at 1 minute sampling rate, csv file download, major event logging |
Network Watchdog | Autonomously ping up to two I.P. addresses and power-cycle output if no response, definable settings |
Power Cycling and Rebooting | Remote on/off control of every output individually |
Auto Restore Mode | Return to previous output settings after a power loss |
Power-up Delay Sequencing | User selectable 0 to 60 second delay between outputs |
Auto Load Shedding | Each output user definable, manual or auto restart |
Environment | |
Operating Temperature Range | -30 C to +60 C |
Cooling | Temperature Controlled Fan |
© Copyright Helios Power Solutions 2022