Our website features a wide range of standard power conversion and backup products, but we also have the capacity and capability to design and manufacture custom solutions to meet your specific application needs. Contact our team of experienced engineers today to discuss your project. Dismiss
The CXC HP HV-ADIO brings advanced control and monitoring to the 125/220Vdc rectifiers and systems. The HV-ADIO is part of the CXC HP series of advanced I/O peripheral incorporating flexible mounting, high accuracy, and the advanced features in the HP control platform.
The HV-ADIO provides a variety of analog inputs, digital inputs and high voltage rated relay outputs. The ADIO device is seamlessly recognized by the CXC HP control platform which also provides advanced setup wizards to create high voltage DC systems .
An integrated Ground Fault Detection (GFD) circuit is also provided to enable visibility to earth leakage currents. This feature can be easily disabled for operators who wish to use 3rd party GFD devices. CXC HP controllers and ADIO peripherals ensure effortless operation and management capability to satisfy the most demanding and advanced energy system applications.
Electrical | |
Input Voltage: | 90 to 300Vdc |
Input power: | 50W (125Vdc 0.4A; 220Vdc 0.2A) |
Output power: | 30Vdc; Max 1A, 30W (For feeding low voltage CXC HP controller) |
DCCT power: | ±15Vdc |
Features | |
Local alarms: | Power ON (Blue) Communications OK (Green) |
Communication ports: | CAN In/Out (RJ12 Offset) |
Ground fault detection: | 1 user configurable (Adjustable up to 15mA) on V2 input channel |
Controller I/O: | |
Voltage inputs: | 2 (±300Vdc) |
Current shunt inputs: | 1 (25 to 200mV) |
DCCT current inputs: | 2 (±10Vdc signal) |
Temperature inputs: | 2 |
Digital inputs: | 4 (Contact closure detect – 5Vdc Max) |
Relay outputs: | 6 (Form C, 220Vdc 50W max) |
Mechanical | |
Mounting: | CXC HP 3U rack panel mount (0180046) or DIN/Panel mounting |
Dimensions: | 198H x 84W x 38D (mm) 7.8H x 3.3W x 1.5D (inches) |
Weight: | 1kg (2lbs) |
Environmental | |
Temperature: | |
Extended: | -40 to 65°C (-40 to 149°F) |
Humidity: | 0 to 95% RH non-condensing |
Elevation: | -500 to +4000m (-1640 to 13124ft) |
Agency Compliance | |
Safety: | CSA C22.2 No 60950-1-03 CE marked |
EMC: | ETSI 300 386 |
Emissions: | CFR47 (FCC) Part 15 Class B ICES-03 Class B EN55022 (CISPR 22) Class B |
Immunity: | EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 |
© Copyright Helios Power Solutions 2024