Glossary of Terminology – Selecting Surge Protection

8/20μs Current Waveshape

A current impulse with a virtual front time of 8μs and a time to half-value of 20μs.

Aggregate Surge Rating

The sum of the surge ratings of individual voltage limiting components, connected in parallel, in the device.

Note: This figure does not indicate the maximum discharge current (Imax) of the device. It does however provide an indication of the expected SPD life. Users should be aware that certain manufacturers may incorrectly claim the aggregate surge rating of MOV material used in their device as its Imax. Non- perfect current sharing between parallel MOVs, and the inability of series over-current or thermal disconnects to carry the full surge current, generally means that the maximum discharge current which the SPD can withstand is less than its aggregate surge rating.

Attenuation

The ability of an SPD to reduce electrical noise interference, measured in decibels. Attenuation varies with frequency, so it is usual to specify the attenuation of the SPD at a particular frequency; commonly 100kHz.

Backup Overcurrent Protection

An external overcurrent protective device installed prior to the SPD. Such a device may be required if the overcurrent limiting device on the service is larger than that required by the SPD or connecting wiring.

Class I test

SPD tested with maximum impulse current (Iimp) and nominal discharge current (In).

Class II test

SPD tested with maximum discharge current (Imax) and nominal discharge current (In).

Class III test

SPD tested with combination wave

Distribution System

Defines the electrical power distribution system. The distribution system is usually described by configuration of the phases, neutral and ground conductor configuration on the secondary side of the supply transformer. Refer to pages 10-12 for further information.

Follow Current (If)

The current supplied by the electrical power distribution system which flows through the SPD after a discharge current impulse. The follow current is significantly higher than the operating current, and is normally high for voltage switching type SPDs (e.g. spark gaps) since the arc voltage falls below the AC supply voltage after firing.

Impulse Current (Iimp)

Peak impulse current withstand with a 10/350μs current waveshape. This is often used for the classification of SPDs tested to Test Class I, but is not the only acceptable waveshape.

Insertion Loss

The insertion loss of an SPD is usually only stated for two port devices for use on low voltage data systems. It is a measure of the ratio of voltage at the output to the input at the device under test. The insertion loss is usually stated for a given frequency and measured in decibels.

Leakage Current

The current flowing to the ground conductor when the SPD is connected to the nominal supply voltage Un.

Let-through Voltage

Another term often used to describe the measured limiting voltage.

Note: This measurement may be carried out with, or without, the presence of the nominal AC power (Un) being applied to the SPD. As such, the results may be different and the user should take cognizance of this in making any comparative assessments.

Location Categories

Various standards attempt to define the electrical environment at which an SPD may be installed, into location categories or zones.

Note: The user should be aware that international consensus has not been reached on these classifications, nor on the size of expected surge activity, which may occur. Further, the user should note that the

demarcation of these zones do not form literal boundaries, but are rather a gradual transition.

Maximum Continuous Operating Voltage (Uc)

The maximum r.m.s. or d.c. voltage which may be continuously applied to the SPD’s mode of protection without degradation or inhibiting its correct operation.

Note: Specifications given in the catalog generally are phase (L-N) voltages.

Maximum Discharge Current (Imax)

The maximum single shot current, having an 8/20μs waveshape, which the SPD can safely divert.

Measured Limiting Voltage

The maximum voltage measured across the SPD’s terminals during the application of an impulse of specified waveshape and amplitude.

Modes of Protection

SPDs may provide protection line-to-ground, line-to-neutral, neutral-to-ground or in combinations thereof. These paths are referred to as the modes of protection.

Note: The user is advised that not all modes require protection, and more is not necessarily better when selecting an SPD. As an example, the N-G mode is not required when the SPD is installed at the primary service entrance of a TN-C-S electrical distribution system, due to the Neutral-Ground bond at this point. The L-L mode is generally not provided for systems with neutral conductors since the L-N modes also protect the L-L modes. Similarly, the L-G mode can be protected via the L-N and N-G modes.

Nominal Discharge Current (In)

The peak value of the current flowing through the SPD during the application an 8/20μs waveshape.

Note: IEC 61643-1requires SPDs tested to Test Class II, to withstand 15 impulses at In followed by 0.1, 0.25, 0.5, 0.75 and 1.0 times Imax.

Nominal (System) Voltage (Un)

The L-N voltage by which an electrical power system is designated. Under normal system conditions, the voltage at the supply terminals may differ from the nominal voltage as determined by the tolerance of the supply system (normally +/- 10%).

One-port SPD

An SPD connected in shunt (parallel) with the circuit to be protected. A one port device may have separate input and output terminals, but without a specific series impedance between these terminals. This type of connection is also known as a Kelvin connection.

Operating Current

The current drawn (per phase) by the SPD when energized at the nominal operating voltage Un.

Note: For SPDs with integral series filtering, the total current drawn may be greater than the real rms current consumption (i.e. VA may be greater than Watts). This is due to the presence of the internal filtering capacitance.

Over-current Protection

An over-current device, such as a fuse or circuit-breaker, which could be part of the electrical distribution system located externally and up-stream of the SPD. May provide protection to the SPD, the connecting wiring and provide a means of externally isolating the SPD.

Protective Earth (PE)

The IEC 60364 series characterizes low-voltage distribution systems by their grounding methods and the configuration of the neutral and protective conductors. The Protective Earth is commonly referred to as “ground”, or “earth”, in many regions.

Rated Load Current (IL)

Maximum continuous rated current that can be supplied to a load connected to the protected output of an SPD. Normally only stated for two port, series connected, SPDs.

Residual Voltage

In IEC terminology this refers to the peak value of the voltage that appears between the terminals of an SPD due to the passage of discharge current In. NZS/AS 1768 refers to this as the let-through voltage, a measurement obtained when the stated test impulse is superimposed on top of the nominal system voltage Un.

Secondary Surge Arrester

A loosely used term given to SPDs intended for operation on medium voltage systems (>1kV). Within the USA,a secondary surge arrester defines an SPD Listed by Underwriters Laboratories Inc. for use on LV and MV systems at locations prior to the main overcurrent disconnect to the facility.

Note: Secondary Surge Arrester Listing is generally considered to have less demanding safety requirements than those for UL 1449 Transient Voltage Surge Arrester Listing.

Short Circuit Current Rating (SCCR)

The short-circuit current rating of the SPD. Required by USA National Electric Code (NEC) for TVSS devices.

SPD Disconnector

An IEC term used to describe a device (internal and/or external) for disconnecting an SPD from the electrical power system.Note: This disconnecting device is not required to have isolating capability. It is to prevent a persistent fault on the system and is used to give an indication of the SPD failure. There may be more than one disconnector function, for example an over-current protection function and a thermal protection function. These functions may be integrated into one unit or performed in separate units.

Spark-over Voltage

The voltage at which a switching type SPD (generally of the spark gap type) will initiate conduction. This value is normally specified for a voltage increasing at 1kV/s.

Stand-off Voltage

The maximum voltage, which can be applied to an SPD, without triggering it into a fully conductive state.

Note: This voltage is normally higher than the maximum continuous operating voltage Uc of the SPD. It is not intended that the SPD be operated at this voltage.

Status Indicator

A device(s) that indicates the operational status of the SPD, or of a particular mode of its protection.

Note: Such indicators may be local with visual and/or audible alarms and/or may have remote signaling and/or output contact capability.

Suppressed Voltage Rating (SVR)

A special case of the measured limiting voltage specific to the UL 1449 Listing of an SPD.

Note: This test is performed using a small 500A 8/20μs current limited impulse, and the clamping voltage recorded at the ends of 6”connecting leads. The result obtained is rounded up to the nearest value given in a table.

Surge Protection Device (SPD)

An IEC term used to describe a device intended to limit transient over-voltages and divert surge currents. It contains at least one non-linear component.

Surge (Reduction) Filter

A two-port series filtering type of SPD specifically designed to reduce the rate-of-rise of voltage (dv/dt) of the pre-clamped waveform. Such a device normally contains a filter with low-pass performance.

Transient Voltage Surge Suppressor (TVSS)

An SPD tested to meet the safety requirements of UL 1449

– Standard for Transient Voltage Surge Suppressors. UL 1449 defines the basic safety requirements for TVSS devices installed on electrical circuits up to 600V. The United States National Electric Code (NEC) only permits TVSS devices to be installed after (downstream of) the main over-current disconnect to a facility.

Two-port SPD

An SPD with two sets of terminals, input and output (line and equipment), and with a specific impedance inserted between these terminals. These are often referred to as series (in-line) connected SPDs and generally contain wave-shaping filters in addition to simple shunt-only protection.

Voltage Protection Level (Up)

Similar to the measured limiting voltage, the voltage protection level characterizes the performance of an SPD in limiting the voltage across its terminals

Note: The voltage protection level is the measured limiting voltage recorded under a specified current magnitude and waveshape, and rounded up to the next highest voltage selected from a list of preferred values found in IEC 61643-1 Standard for surge protective devices connected to low-voltage power distribution systems. For SPDs tested to Test Class I, Up is generally stated using a 10/350 Iimp and for SPDs tested to Test Class II, using an 8/20μs Imax.